    Problem Description

    It has been reported that the XDLC Module has had instances where the card fail LED has
    been seen lit on the card but does not post a trouble back to the PMI (this is found on
    Modular systems with Zeus rev 14.01 and 14.02).

    The Field is also reporting that the XDLC Module is posting intermittent Device
    Communication Loop Fail troubles (along with card fail LED), which can be found on Zeus
    rev 14.03 systems.

    Although, it can cause these nuisance trouble activities on the system, testing has
    determined that it does not affect the ability of the card to respond in an alarm condition or
    other off-normal conditions.

    Problem Explanation

    Initially we had seen that customers had been returning failed XDLC cards with illuminated
    CARD FAIL LEDs. No fault messages associated with this trouble were reported at the PMI
    panel.

    From the initial investigation, It was found that a trouble flag bit was being sent from the
    XDLC’s to the PMI, but this flag was not associated with any PMI messages, so it was not
    reported at the panel. As a result, a FW change was implemented and released in early 2020
    as part of the Modular’s Market Release MR1.2. The XDLC application FW (ver. 1.1.6) was
    updated to associate this flag with an existing trouble message; “DEVICE
    COMMUNICATION LOOP FAULT”.

    As a result, the fault was visible, and customers started reporting the issue more frequently.
    After that change, fault messages started to come in and out intermittently and we started to
    see reports at several locations that caused us to further investigate.

    the investigation into the issue has determined that a quality issue with a particular IC chip
    has resulted in XDLC boards potentially experiencing this condition. The quality issue stems
    from the presence of moisture found in one of the IC Chips used on the XDLC board
    The issue seems to be most apparent on XDLC cards that are wired in a Class B
    configuration and with more heavily populated circuits (greater than 180 devices) but is not
    limited to those parameters.

    The suspect IC could have been used in manufacturing within the period of 2018 through
    mid-2020 but tracking down to this level is not done, so we do not have an exact
    manufacturing window or date-code range that is affected.

    Solution

    Siemens is advising customers if they have an XDLC Module exhibits the Device
    Communication Loop Fault troubles or Card Fail LED lit, to replace it. Returned boards and
    replacements can be handled by the normal RMA and Special Labor Relief processes
    currently in place. Contact your dedicated Customer Service Rep .
    Special Labor Relief Program details can be found in PLN PI-07-20

    Affected Parts

    Model Ordering # Description Trade Net
    XDLC S54430-B8-A1 INTELLIGENT DEVICE LOOP CARD FOR

    All XDLC Modules exhibiting the issue and purchased within the range mentioned above
    must be returned no later than December 31, 2022 to qualify for the replacement credit.